GeneralUltraSens develops and implements telemetry solutions based on module R-Log. The R-LOG remote data logger is a general purpose GSM/GPRS Remote Terminal Unit (RTU) Logger for telemetry that contains a massive data logger. No matter where you are in the world, logged data can be sent straight to your Email box. In addition, data can be sent (SMS) to your cell phone to provide you with crucial information instantly. It can directly communicate with an SMTP server to send some or all of its logged data to predefined email boxes. In addition, the R-LOG provides 24/7 global communication coverage for automatic SMS alert messages, SMS I/O inquiries and SMS I/O settings. Versatile, reliable and quickly configured, the R-LOG is a cost effective DIN rail mountable RTU Logger, featuring up to 6 A/I, 8 D/I, 2 D/O, 1 EIA RS232 serial port and automatic email dispatch service. |
|
Configuration softwareThe R-Tec is all-in-one, easy-to-use configuration software. It provides a user-friendly environment for RTU configuration and Logged data manipulation. The R-Tec includes RTU configuration tools, Mail Retrieval Agent (MRA), data parser and online calibration tools. It supports both local and remote download for easy PC - RTU data transformation. The powerful remote download mechanism simplifies the downloading process, and can carry out multiple unit download processes in one GSM session. The smart calibration tool can establish data communication with the R-LOG, to display the current values and to help you in carrying out your desired calibration. | ![]() |
Communication
The R-LOG utilizes the popular GSM/GPRS network to transmit and receive data. No need to get expensive antennas, frequency licensing or power consuming radio transmitters. No need to be dealing with transmission interruptions or be worried about distance limitations. Simply use the R-LOG to get highly effective communication results, saving you time and money.
External Devices
The R-LOG can either be used as a standalone unit or it can be connected to a PLC. When connected to a PLC, the R-LOG controls the PLC I/Os and registers. It serves as a cellular gateway for establishing mobile communication between you and your PLC; delivering a complete, interactive, mobile communication and Email log service. Adjustable, reliable and easy-to-use, the R-LOG is a versatile PLC interfaced communication tool; supporting Modbus, Unitronics, Hostlink and many other serial communication protocols.
Settings
The R-LOG remote data logger provides both automatic and user-interference services. Using the R-Tec you are free to configure the automatic behavior of the R-LOG to meet your needs. The R-LOG built-in, user-interference system makes it possible to set/get registers and I/O values from the comfort of your mobile-phone. You can simply send an SMS message to turn the digital-output on/off, get I/O values, set the time and date, set/get register values and more.
Supervising and managing
Supervising and managing your system has never been easier; all management activities can easily be done from the comfort of your cell phone. Analyzing and Logging data has become elegantly simple. Logged data can be sent directly to POP3 servers enabling virtually infinite data capacity and making it more accessible, manageable and meaningful.
Specifications
HW interfaces | |
RS-232 | One DB9 male (standard EIA) |
Digital Inputs | 8 (5-24VDC) |
| Analog Inputs | 2 Current (0-20mA) |
| Digital Output | 2 (Relay 5A) |
| Leds | 4 yellow |
Physical Characteristic | |
Dimension | 105X63X90mm |
Weight | 240gr |
Cover | Rigid plastic – Lexan 920 |
Assembly | Appropriate for mounting On DIN 35mm Rail |
| Power supply Specification | |
| Power supply | 12-24VDC |
| Maximum momentary power failure | 10mS |
| Maximum power consumption | 24W(1A) |
| Typical power consumption | While transmit 1.8W no transmit 1.1W |
| Current consumption at 12V Continues | 90mA |
| Environment | |
| Operating Temperature | -25ºC to 55ºC |
| Storage Temperature | -40ºC to 85ºC |
| Operating Humidity | 5% to 95% Non-condensing |
| Protocols | |
PLC protocols | MODBUS, Matusushita, Unitronics, Omron, IZUMI and others |
| Memory Specification | |
| Total Size | 2MB flash memory |
| Logger memory size | 1.5MB from flash memory |
| Events memory size | 0.4MB from flash memory |
| Internal use memory size | 0.1MB from flash memory |
| Sample rate | 1sec – 1 day |
| Period | 5 days – 5 years |
| Download data methods | Email – via GPRS/SMTP GSM – via CSD session |
| Data structure | EXCEL file |
| Voltage analog input Specification | |
| Number of input | 2 |
Resolution bit | 10 bit (10mV) |
Conversion speed | 10mS |
Input voltage | 0-10VDC |
Precision | 2% (20mV) |
Input impedance | 619KΩ (10%) |
Offset/Gain
| Offset value- 0 at 0VDC GAIN value: 0-10V= 0-1024 / 65535 |
| Current analog input Specification | |
| Number of input | 2 |
Resolution bit | 10 bit (0.02mA) |
Conversion speed | 10mS |
Input voltage | 0-20mA DC |
Precision | 2% (0.4mA) |
Input impedance | 200Ω (10%) |
Offset/Gain | Offset value- 0 at 0mA GAIN value: 0-20mA=0-1024 / 65535 |
| PT100 analog input Specification | |
| Number of input | 2 |
PT100 range | (-20) - (80) |
Resolution bit | 8 bit (0.3ºC) |
Conversion speed | 10mS |
Precision | Worst case 0.4ºC |
Input impedance | 20KΩ |
Connection options | Three (compensation) or two wires |
| Isolation | None |
| Cellular Network Interface | |
Band | Quad-Band EGSM 850/900/1800/1900 MHz |
Protocols | CSD, SMS, GPRS class 10, Mobile station class B |
Internal modem | Telit 864 |
Modem Approvals
| Fully type approved according to R&TTE CE, GCF, FCC, PCTRB, IC |
Technology | GSM network + SIM card |
| DC input Specification | |
Number of input | 8 |
Number of com | 2 |
Input voltage | 12-24V |
| Input current | 5 mA 24 VDC |
Off/On | >5.2V |
On/Off | <4.2V |
Response time | 10mS |
Frequency maximum | 50Hz |
Minimum pulse width | 80μs |
Isolation | Optocoupler |
| Output Specification | |
| Number of output | 2 |
Output type | Relay for 0-30 VAC/VDC |
Max resistive load | 5A 30 VDC |
Contact life cycle | 100,000 operations minimum (contact rating) |
Minimum load | 150W |
Maximum inductive load | 1250 VA |
Response time | 6mS |
Isolation | By relay 1G Ω |